Component | Visual and Functional inspection |
Safety valves for steam generators with fully demineralized water and hot water generators in general | Check ease of movement |
Water level controller transmitters after commissioning and water quality disturbances | Check on ease of movement and inspect state of internal cleaning |
Flow limiters | Check effectiveness by reducing flow rate |
Pressure indicator connecting piping | Check water pressure, pressure gauge .Passage cleaning |
Pressure limiters connecting piping | Check effectively switch points,passage cleaning |
Pressure stats connection piping | Check switch on/off points,passage cleaning |
Temperature indicators Sensors | Check water prescis. thermometer inspection |
Temperature regulators Sensors | Check switch on/off point inspection |
Temperature limiters Sensors | Check effectively switch points inspection |
Draining and blow down Equipment | Inspection |
Boiler valves and components | General inspection |
Feeding and circulation equipments | Inspeaction |
Feed/fill and make-up water treatment plant, Boiler/circulation wter | Check for proper state,Assessment of operating conditions and water condition |
Flue gas damper limiters switch | Close/switch-off test |
Combustion air fans, ignition and/ or cooling air fans | Check wear, cleaning, power transmitters, lubrication |
Air pressure stats | Pulse interruption |
Fuel pressure indicators | Check water pressure and pressure gauge |
Safety shut off devices before burner | Tightness test,Check ease of movement |
Tightness checking equipment of internal vent of flue gas firing | Check effectiveness and cleaning |
Burner start,position swithc | Switch off test |
Emergency-off switch | Test by actuation |
Ignition equipment, Electrodes,Burners | Electrodes and valve state,Cleaning |
Ventilation of flue gas passes | Check ventilation time |
Flame monitoring system and flame sensors | Effectiveness check by darkening the sensor,Cleaning |
Assessment of the combustion and boundary valves check | measurements of check flue gas quality and fuel throughput |
Assessment of the furnaces and the flue gas passes | Check insulation lining and cleaning state |