Motor Starter
The
starter also complies with the following specification as the standard.
Accordingly, when the starter is purchased from a manufacturer other than our
Company, the starter shall meet the same specification.
2.1
Structure of starter
The
casing box shall be of steel make, drip-proof, wall-hanging type. Installation
shall be made on rear side at four upper and lower corners of the casing box
and shall be round holes for upper part and slots for lower part so as to
permit easy installation. Further, for introduction of external wires, comings are
provided.
2.2
Components
Ammeter,
push buttons and indicating lights are installed at the door and
electromagnetic contactor, overload relay, time limit relay, auxiliary relay,
fuse and terminals, etc., in the box.
2.2.1 Ammeter
The
ammeter able to measure current directly above or approx. 120% of rated
current, with the maximum scale of 3-time extension, is employed.
On
the other hand, as the ammeter is required to monitor the operating conditions
of SELFJECTOR, it must be installed.
2.2.2 Overload relay (thermal relay)
This
shall be of a manual return type with time limit characteristics, and the
current settings shall be rated current values given in Table 4.3.
2.2.3 Time limit relay (timer)
In
connection with the characteristics of SELFJECTOR. Starting current of the
following types will be over current of about 150% for several minutes at the
time of start-up, so a division circuit is provided for prevention of actions
of overload relay by installing Timer (variable timer for 10 minutes).
2.3
Wiring of starter
For reference, the SELFJECTOR starter internal
connection at AC 440V is shown in Fig. below.
NOTE
|
|
1. Terminals No. PR, PC and PA serve
for external indication and shall be connected to monitor panel.
2. Terminals MI 1, 12, MI, 5 and M6.10
are to be connected to the automatic control panel.
|
No comments